134Hz %14 3x400V DETUNED HARMONIC REACTORS
Machines, tools and the other electrical devices which are used in the industry, facility and the other structures cause harmonic pollution. Filtered compensation system must be used to minimize this pollution. Therefore, the reactors which are recommended to be used in the compensation systems are connected to the power capacitor in the system in serial.
BENEFITS OF REACTOR
-
It protects the System against the risk of harmonic resonance.
-
Reactors provides trouble-free operation and extend the life of the Capacitors, contactors or thyristors.
-
Provides Enegry saving.
TECHNICAL SPECIFICATIONS
| Standards |
IEC 60076-6/60289/61558-2-20 |
| Busbar Voltage |
230VAC – 1000VAC |
| Power |
1.0kVar – 100kVar |
| Energy Frequency |
50 – 60Hz |
| Inductance Settings |
± %4 |
| Insulation Test |
3.0Kv 1 min |
| Insulating Class |
F – 155 C |
| Protection Class |
IP 00 |
| Transformer Plate |
1.20 w/kg Silisli Sac |
| Contact Thermostat |
120 ºC |
| Application |
Closed Area |
| Ambient Temperature |
-15 ºC / +40 ºC |
| Cooling |
Natural (Air Cooling) |
| Design |
Air-Gap |
| Connector |
Terminal – Busbar |
| Winding Material |
AL-CU |
SELECTION TABLE


SELECTION TABLE OF BUSBAR VOLTAGE 400V CAPACITORS